Publication

Mitigation of Harmonic Voltage Amplification in Offshore Wind Power Plants by Wind Turbines With Embedded Active Filters

Emerson David Guest, Kim Hoj Jensen, Tonny Wederberg Rasmussen

IEEE Transactions on Sustainable EnergyMar 21, 2019
Abstract

In this paper, active filters are embedded in the grid-connected converter control of Type-IV wind turbines to reduce harmonic voltage amplification in offshore wind power plants (WPPs). The extra element theorem is employed to tune the active filters and determine the stability margin. Active filter tunings that satisfactorily reduce harmonic voltage amplification yet provide sufficient stability margin in the augmented system are identified. A running example is performed on a 270 MW offshore WPP comprised of 3-MW wind turbines implemented in real-time simulation as hardware-in-the-loop. Both converter and grid voltage harmonics are suppressed at WPP buses to below the stipulated planning levels.

1Authors

AuthorAffiliationh-indexCitations
Emerson David GuestSiemens Gamesa Renewable Energy, Lyngby, Denmark6133
Kim Hoj JensenSiemens Gamesa Renewable Energy, Lyngby, Denmark13533
Tonny Wederberg RasmussenTechnical University of Denmark10331

Showing the abstract — retrieve the full paper via the Exa API.